Dlp-G590 Mount The Ons 15454 M2 Shelf On The Wall - Cisco ONS 15454 Hardware Installation Manual

Hide thumbs Also See for ONS 15454:
Table of Contents

Advertisement

Installing the ONS 15454 M2 Shelf
Figure 130: Mounting an ONS 15454 M2 in a Rack
Step 3
Lift the shelf to the desired position in the rack.
Note
Step 4
Align the screw holes on the mounting brackets with the mounting holes in the rack.
Step 5
Using the Phillips Dynamometric screwdriver, install one mounting screw in each side of the assembly.
Tighten the screw to a torque value of 22 in-lb (2.5 N-m).
Step 6
When the shelf is secured to the rack, install the remaining two mounting screws on either sides of the shelf.
Step 7
Return to your originating procedure (NTP).

DLP-G590 Mount the ONS 15454 M2 Shelf on the Wall

Purpose
Tools/Equipment
Prerequisite Procedures
Required/As Needed
Onsite/Remote
Security Level
To ensure proper cooling of the ONS 15454 M2 shelf, make sure that the space in front of the air
flow vents are free of cables, fibers, and mechanical fixtures for fiber and cable management.
This task explains how to mount the ONS 15454 M2 shelf on the wall.
• # 2 Phillips Dynamometric screwdriver
• 6 pan-head Phillips mounting screws
NTP-G305 Unpack and Inspect the ONS 15454, ONS 15454 M2, and ONS 15454
M6 Shelves, on page
As needed
Onsite
None
DLP-G590 Mount the ONS 15454 M2 Shelf on the Wall
20.
Cisco ONS 15454 Hardware Installation Guide