6.2

Replacing modules (spare part scenario)

6.2.1

Spare parts replacement for SIMOTION D410

Use of used modules
If a used D410 is used for the module replacement, we recommend that the retained data be
deleted from the used D410.
Two options are available for this.
Table 6-1
Option
Module memory reset
Deleting and restoring non-
volatile SIMOTION data
NOTICE
Unintentional restoration of the default settings instead of memory reset
When the operating mode switch is set to switch position S1/S2/S3 = OFF (MRES), switching
the power OFF/ON performs "Restore default settings" instead of "Memory reset."
To avoid and unintentional/accidental deletion of the project data on the CF card, we
recommend that the retain data be deleted via the service selector switch.
SIMOTION D410
Commissioning Manual, 04/2014
Options for deleting the retain data
Reference to description
See Section Resetting the memory of
SIMOTION D410 (Page 152)
See Section Deleting/restoring non-
volatile SIMOTION data (Page 209)
Maintenance and service
6.2 Replacing modules (spare part scenario)
Notes
Control via an operating mode
switch (setting MR).
This is available on all
SIMOTION platforms
Control via a service switch. Is
only available on SIMOTION D.
167