Siemens SINUMERIK 840D sl Function Manual page 725

Safety integrated
Hide thumbs Also See for SINUMERIK 840D sl:
Table of Contents

Advertisement

C01711
SI Motion P1 (CU): Defect in a monitoring channel
For fault value = 5012:
Check the setting of the PROFIsafe address of the Control Unit (p9610) and that of the Motor Modules
(p9810). The PROFIsafe address must not be 0 or FFFF!
For fault value = 5013, 5025:
Carry out a POWER ON (power off/on) for all components. Check the setting of the PROFIsafe address of
the Control Unit (p9610) and that of the Motor Modules (p9810).
Check whether there is a DRIVE-CLiQ communication error between the Control Unit and the Motor Module
involved, and if required carry out a diagnostics routine for the faults identified.
For fault value = 5022:
Check the value settings of the F-parameters at the PROFIsafe slave (F_SIL, F_CRC_Length, F_Par_Ver‐
sion, F_Source_Add, F_Dest_add, F_WD_Time).
For fault value = 5026:
Check the value settings of the F-parameters and the F-parameter CRC (CRC1) calculated from this value
at the PROFIsafe slave and update.
For fault value = 5065:
Check the configuring and communication at the PROFIsafe slave (Consecutive No./ CRC). Check the value
setting of the F-parameter F_WD_Time at the PROFIsafe slave and possibly increase.
Check whether there is a DRIVE-CLiQ communication error between the Control Unit and the Motor Module
involved, and if required carry out a diagnostics routine for the faults identified.
Safety Integrated
Function Manual, 12/2017, 6FC5397-4BP40-6BA1
11.3 Safety messages for SINAMICS S120
Diagnostics
725