Connecting sensors and actuators
8.5 Safe programmable logic
; End of program
M17
These instructions simulate the output interfaces of the NCK-SPL and therefore "short-circuit"
the crosswise data comparison.
Commissioning
The logic used in this phase has a single channel structure and is therefore not safe!
The described minimum NCK-SPL must be replaced by a full NCK-SPL without any access
to $A_INSIP(D), ..., $A_MARKERSIP(D) when the PLC side is completed!
Additional diagnostic support:
● $A_STATSID: A value not equal to 0 means that an error has occurred in the crosswise
data comparison.
● $A_CMDSI[n]: n=1: 10x change timer value for long forced checking procedure pulses and/
or single-channel test stop logic.
● $A_LEVELSID: Indicates how many signals have different signal levels on the NCK and
PLC sides that can be presently detected.
● In addition, other NC variables or free R parameters can be written to monitor internal states
of the SPL.
The following applies to all system variables of the NCK-SPL outputs: They can be written from
and read back to the SPL program.
See also
SPL data on the PLC side (Page 288)