Status Subsystem Commands; Subsystem Syntax - Keysight Technologies 6811C Programming Manual

Ac power solutions
Hide thumbs Also See for 6811C:
Table of Contents

Advertisement

3
Language Dictionary

Status Subsystem Commands

This subsystem programs the ac source status registers. The ac source has three
groups of status registers; Operation, Questionable, and Standard Event. The
Standard Event group is programmed with Common commands. The Operation
and Questionable status groups each consist of the following five registers:
– Condition
– Enable
– Event
– NTR Filter
– PTR Filter
Refer to
"Programming Examples"

Subsystem syntax

STATus
168
"Programming the Status Registers"
:PRESet
Presets all enable and transition registers to power-on
:OPERation
[:EVENt]?
Returns the value of the event register
:CONDition?
Returns the value of the condition register
:ENABle <n>
Enables specific bits in the Event register
:NTRansition <n> Sets the Negative transition filter
:PTRansition <n> Sets the Positive transition filter
:QUEStionable
[:EVENt]?
Returns the value of the event register
:CONDition?
Returns the value of the condition register
:ENABle <n>
Enables specific bits in the Event register
:NTRansition <n> Sets the Negative transition filter
:PTRansition <n> Sets the Positive transition filter
Keysight Models 6811C, 6812C, and 6813C Programming Guide
on page 259 in
for more information.
Chapter 5,