List:ttltrg:points; List:voltage - Keysight Technologies 6811C Programming Manual

Ac power solutions
Hide thumbs Also See for 6811C:
Table of Contents

Advertisement

LIST:TTLTrg:POINts?

This query returns the number of points specified in LIST:TTLT. Note that it returns
only the total number of points, not the point values.
Returned parameters <NR1>

LIST:VOLTage

This command specifies the output voltage points in a list. The voltage points are
given in the command parameters, which are separated by commas. The order in
which the points are entered determines the sequence in which they are output
when a list is triggered. Changing list data while a subsystem is in list mode
generates an implied ABORt.
The maximum peak voltage that the ac source can output is 425 V
includes any combination of voltage, voltage offset, and function shape values.
Therefore, the maximum value that can be programmed depends on the
peak-to-rms ratio of the selected waveform. For a sine wave, the maximum
voltage that can be programmed is 300 V
Returned parameters <NR3>{, <NR3>}
Keysight Models 6811C, 6812C, and 6813C Programming Guide
Query syntax [SOURce:]LIST:TTLTrg:POINts?
Examples
LIST:TTLT:POIN?
Related commands LIST:TTLT
Command syntax [SOURce:]LIST:VOLTage[:LEVel] <NRf+>{, <NRf+>}
Parameters For sine waves: 0 to 300 | MAXimum | MINimum
Unit V (rms voltage)
Examples
LIST:VOLT 115, 126, 120
Query syntax [SOURce:]LIST:VOLTage[:LEVel]?
Related commands LIST:VOLT:POIN?
LIST:VOLT:SLEW
Language Dictionary
.
rms
LIST:VOLT MAX, 120, MIN
LIST:COUN
LIST:DWEL
LIST:VOLT:OFFS
3
. This
peak
LIST:STEP
143

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6812c6813c

Table of Contents