Status:questionable - Keysight Technologies 6811C Programming Manual

Ac power solutions
Hide thumbs Also See for 6811C:
Table of Contents

Advertisement

3
Language Dictionary
Bit configuration of Questionable Status registers
Bit position
15
Bit name
n.u.
Bit weight
16384
n.u. = Not used
OV = Overvoltage protection has tripped
OCP = Overcurrent protection has tripped
SOA = Safe operating area protection has tripped
UNR = Output is unregulated
OT = Overtemperature protection has tripped
RI = Remote inhibit is active
CL peak = Peak current limit is active
Rail = Rail protection tripped
CL rms = rms current limit is active
MeasOvld = Current measurement exceeded low current range capability

STATus:QUEStionable?

This query returns the value of the Questionable Event register. The Event register
is a read-only register which holds (latches) all events that are passed by the
Questionable NTR and/or PTR filter. Reading the Questionable Event register
clears it.
Returned parameters <NR1> (register value)
172
14
13
12
Meas
CL
n.u.
Ovld
rms
4096
Query syntax STATus:QUEStionable[:EVENt]?
Parameters None
Examples
STAT:QUES:EVEN?
Related commands *CLS
Keysight Models 6811C, 6812C, and 6813C Programming Guide
11
10
9
CL
Rail
RI
peak
2048
1024
512
STAT:QUES:NTR
8 – 5
4
3
n.u.
OT
UNR
16
8
STAT:QUES:PTR
2
1
0
SOA
OCP
OV
4
2
1

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6812c6813c

Table of Contents