Pararmeters Setting Manual; Parameter Settings - Smartgen HGM8110DC-2 User Manual

Genset controller
Table of Contents

Advertisement

Power factor Conditions Active power Inactive power
COS>0L
P>0,Q>0
COS>0C
P>0,Q<0
COS<0L
P<0,Q>0
COS<0C
P<0,Q<0
Remark:
1.
Input active power, generator or mains supply electricity to load.
2.
Output active power, load supply electricity to generator or mains.
3.
Input reactive power, generator or mains send reactive power to load.
4.
Output reactive power, load send reactive power to generator or mains.
★DC GENS, includes as below,
Voltage, current, power and accumulated energy
★Alarm:
Displays all alarm information, including warning, alarm shutdown, trip shutdown and trip.
NOTE: For ECU warning and shutdown alarms, if the detailed alarm information is displayed, check engine according to it,
otherwise, please check the manual of generator according to SPN alarm code.
★Event log
Records all start/stop events (shutdown alarm, trip and stop alarm, manual /auto start or stop) and the real
time when alarm occurs.
★Others, includes,
Time and Date, count down time for maintenance, input/output ports status, NET status etc.
★About, includes,
Released software and hardware versions and PD number of controller

5.3.2 PARARMETERS SETTING MANUAL

Press
to enter user menu;
Configure:After entering the correct password (factory default password is 00318) you can enter
parameter settings screen.
Language:Selectable Chinese, English and others (default: Espanol)
Test Run:On load, off load and custom commissioning are optional. Custom commissioning can be
configured to on load or not during commissioning, commissioning time and which mode to return to
after commissioning (manual mode, auto mode and stop mode).
Clear accumula.:Can clear total running time A and B, total electric energy A and B.

5.3.3 PARAMETER SETTINGS

DC generator settings
Timers settings
Engine settings
AC Generator settings
AC Load settings
Breaker settings
HGM8110DC-2 Genset Controller
HGM8110DC-2 GENSET CONTROLLER USER MANUAL
Table 7 - Power Factor Descriptions
Input
Input
Input
Output
Output
Input
Output
Output
2020-02-20
Remark
Load is inductive resistance.
Load is capacitance resistance.
Load equals to one under excitation
generator
Load
equals
to
one
generator.
Version 1.0
over
excitation
Page 15 of 69