Definition And Range Of Parameters; Parameter Settings - Smartgen MGC120 User Manual

Petrol genset controller
Hide thumbs Also See for MGC120:
Table of Contents

Advertisement

7 DEFINITION AND RANGE OF PARAMETERS

7.1 PARAMETER SETTINGS

Paramerters which can be configured by the controller are as follows,
No.
Items
P00 Mains Normal Delay (0-3600)s
Mains
Abnormal
P01
Delay
Mians Under Volt
P02
Value
Mains
Over
P03
Value
P04 Transfer Delay
P05 Mains Options
P06 Start Delay
P07 Stop Delay
P08 Start Attempts
P09 Cranking Time
P10 Crank Rest Time
P11 Safety On Delay
P12 Warming Up Time
P13 Cooling Time
P14 ETS Solenoid Hold
P15 Close Time
P16 Engine Cylinders
MGC120 Petrol Genset Controller
Parameter Range Default
(0-3600)s
(30-360)V
Volt
(30-360)V
(0-99.9)s
(0-1)
(0-3600)s
(0-3600)s
(1-10)
(3-60)s
(3-60)s
(1-60)
(0-3600)s
(3-3600)s
(0-120)s
(0-10.0)s
(1-2)
Version 1.0
MGC120 Petrol Genset Controller User Manual
10
Time duration for confirming mains voltage
from abnormal to normal or from normal to
5
abnormal, it is used to switch ATS.
it is considered mains under voltage if
sample voltage is lower than the set value.
184
When 30V is set, there is no under voltage
detection.
it is considered mains over voltage if sample
voltage is higher than the set value. When
276
360V is set, there is no over voltage
detection.
it is time interval for transferring switch from
1.0
mains open to generator close or from
generator open to mains close.
0:AMF(mains abnormal start enabled in
auto mode)
0
1: Display Only (only monitoring mains
voltage)
Time duration from remote start signal is
1
active to engine startup.
Time duration from remote start signal is
1
deactivate to engine stop.
It is maximum of start attempts when starter
3
failed to start. When reaches set attempts
the fail to start alarm will be initiated.
8
Time of starter every time power up.
The waiting time before second power up
10
when engine starts fail.
Alarms for low oil pressure under frequency
10
and under voltage are deactivated.
Warming time between genset close and
10
high speed running.
Radiating time before stop genset, after it
10
unloads.
Stop electromagnet's power on time when
20
pump unit is stopping.
Pulse width of mains close and generator
0
close. 0s stands for constant output.
it is used for judging starter disconnect
1
conditions and detecting engine speed.
2017-11-07
Description
Page 11 of 19