R&S NGL200 Series User Manual page 141

Hide thumbs Also See for NGL200 Series:
Table of Contents

Advertisement

®
R&S
NGL200/NGM200
Example:
DIO:FAULt:SOURce <arg0>
Sets or queries the "operation modes" of the digital output fault source
See "operation modes" in
Parameters:
<arg0>
Example:
DIO:FAULt[:STATe] <arg0>
Enables or disables the digital output fault.
See "operation modes" in
Parameters:
<arg0>
Example:
DIO:OUTPut:SOURce <arg0>, <arg1>
DIO:OUTPut:SOURce? <arg0>
Enables or disables the digital output source.
See "operation modes" in
Parameters:
<arg1>
Parameters for setting and query:
<arg0>
User Manual 1178.8736.02 ─ 05
DIO:FAUL:CHAN 1
Sets channel 1 as the output fault source.
Figure
6-18.
CC | CV | CR | SINK | PROTection
DIO:FAUL:SOUR PROT
Sets the "operation modes" of the digital output fault source as
protection. If any of the protection modes (OCP, OCP, PPP, OTP
and Sense) of the digital output fault source is active, a trigger
event is triggered to the trigger-out signals on the instrument.
Figure 6-18
1 | 0
DIO:FAUL 1
Enables the digital output fault.
Figure
6-18.
OUTPut | TRIGger | FORCed
OUTPut
Selected channel output is used as the digital output source.
TRIGger
Selected channel external trigger signal is used as the digital
output source.
FORCed
Selected output is forced to high level and can be switched by
DIO:OUTPut[:STATe]
1 | 2
Channel selection for the digital output source.
Remote Control Commands
Advanced Operating Commands
on page 139 command.