YASKAWA FSDrive-MV1000 Series Instructions For Use Manual page 161

Super energy-saving medium-voltage ac drive
Hide thumbs Also See for FSDrive-MV1000 Series:
Table of Contents

Advertisement

Digital Operator Display
Uv1
Cause
Input power phase loss
One of the drive input power wiring terminals is
loose.
There is a problem with the voltage from the
drive input power.
The power has been interrupted.
Digital Operator Display
Uv3
Cause
There is an error in the in-rush prevention circuit
breaker.
There is an error in the in-rush prevention panel
control power.
The breaker close command is not being input to
the in-rush prevention panel.
Digital Operator Display
VUB
Cause
The motor has been damaged due to overheating
or the motor insulation is damaged.
One of the motor cables has short circuited or
there is a grounding problem.
The output side cable wiring is incorrect.
<1> When a fault occurred at the startup of the drive, CPF00 or CPF20 is displayed. When a fault occurred after the startup, CPF01 or CPF21 is
displayed.
Option Card
SI-N3, SI-P3, AI-A3, DI-A3
PG-B3, PG-X3
DO-A3, AO-A3
<1> When used for monitoring, AI-A3 and DI-A3 can be installed in any of CN5-A, B or C.
<2> Use port CN5-C when connecting one PG option card. Use ports CN5-B and CN5-C when connecting two PG option cards.
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
Undervoltage
One of the following conditions occurred while the drive was operating (during voltage output):
• Voltage in the DC bus fell below the undervoltage detection level (L2-05)
• 2 kV class: Approx. 693 V
• 3 kV class: Approx. 940 V
• 4 kV class: Approx. 1188 V
• 6 kV class: Approx. 1188 V
• 11 kV class: Approx. 1188 V
• Check that the main circuit drive input power is wired incorrectly.
• Correct the wiring.
• Ensure there are not loose terminals
• Retighten the terminals to the tightening torques specified in this manual.
Gauges and Tightening Torques on page 91
• Check the voltage.
• Correct the voltage to be within the range listed in drive input power specifications.
• If there is no problem with the power supply to the main circuit, check for problems with the
main circuit breaker.
Correct the drive input power.
In-rush Prevention Circuit Error
A malfunction has occurred in the in-rush prevention circuit.
• Check the breaker maintenance period in U4-06 (in-rush prevention circuit breaker).
• Replace the breaker if it has reached the end of its service life, or has failed. Maintenance
settings are performed in o4-07.
• Check that there are no wiring breaks or miswirings in the control power wiring.
• Perform wiring correctly.
• Check that there are no wiring breaks or miswirings between the drive and the in-rush
prevention panel.
• Check that there are no errors in the drive contact outputs.
• Perform wiring correctly or replace the relay board.
Voltage Unbalance
The sum of the detected output voltages of the three phases exceeded the detection level for
longer than the stipulated time.
Check the insulation resistance of the motor. Replace the motor.
Check the motor cable. Remove the short circuit and reapply power.
Check the resistance between the motor cables and the ground terminal
Replace the cable.
Correct the wiring.
Table 5.13 Option Card Installation
Available Port/Connector
<1>
CN5-B, C
CN5-A, B, C
Fault Name
Possible Solutions
for details.
Fault Name
Possible Solutions
Fault Name
Possible Solutions
CN5-A
<2>
5.4 Fault Detection
Refer to Wire
.
Number of Option Cards Possible
1
2
1
5
161