5.6 Operator Programming Error
Digital Operator Display
oPE07
Cause
At least two analog input terminals are set to the same
function (i.e., at least two of these parameters has the
same setting: H3-02 and H3-10).
The following simultaneous contradictory settings:
H3-02 and H3-10 = C (PID Target Value) while b5-18 = 1
(enables b5-19 as the target PID value)
Digital Operator Display
oPE08
Cause
Attempted to use a function that is not valid for the
selected control mode.
In Open Loop Vector Control, n2-02 is greater than n2-03. Correct parameter settings so that n2-02 is less than n2-03.
In Open Loop Vector Control, C4-02 is greater than
C4-06.
Note: Use U1-18 to find which parameters are set outside the specified setting range. Other errors are given precedence over oPE08
when multiple errors occur simultaneously.
Digital Operator Display
oPE09
Cause
The following simultaneous contradictory settings have
occurred:
• b5-15 not 0.0 (PID Sleep Function Start Level)
• The stopping method is set to either DC Injection
Braking or coast to stop with a timer (b1-03 = 2 or 3).
When b5-01 = 1 or 2 (PID output 1/2), d2-02 (Frequency
Reference Lower Limit) ≠ 0 was specified.
When b5-01 = 1 or 2 (PID output 1/2), b5-11 (PID Output
Reverse Selection) = 1 (Rotation direction reverses with
negative PID output) was specified.
PID control is set to b5-01 = 3 or 4, but the lower limit for
the frequency reference (d2-01) is not 0.
Digital Operator Display
oPE10
Cause
V/f Pattern Setting Error
172
Multi-Function Analog Input Selection Error
A contradictory setting is assigned to multi-function analog inputs H3-02 or H3-10 and
PID functions conflict.
Change the settings to H3-02 and H3-10 so that functions no longer conflict.
Note: Both 0 (frequency reference bias) and F (not used) or 1F (Through mode) can be
set to H3-02 and H3-10 simultaneously.
Disable one of the PID selections.
Parameter Selection Error
A function has been set that cannot be used in the motor control method selected.
Check the motor control method and the functions available.
Correct parameter settings so that C4-02 is less than C4-06.
PID Control Selection Fault
PID control function selection is incorrect. Requires that PID control is enabled
(b5-01 = 1 to 4).
Set b5-15 to another value other than 0.
Set the stopping method to coast to stop or ramp to stop (b1-03 = 0 or 1).
Correct the parameter settings.
Correct the parameter settings.
Correct the parameter settings.
V/f Data Setting Error
One of the following setting errors have occurred:
• E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤ E1-04
• E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤ E3-04
Correct the settings for E1-04, E1-06, E1-07, E1-09, and E1-11. For motor 2, correct
E3-04, E3-06, E3-07, E3-09, and E3-11.
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions
Error Name
Possible Solutions

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-mv2 series

Table of Contents