Operation Procedure of Copy Function (Digital Operator)
n
The digital operator will allow the following operations depending on the setting for parameter o3-01, Copy Function
Selection:
INV → OP READ (o3-01 = 1)
Stores the parameter settings of one drive in the digital operator.
Note: The number of the read operations of the digital operator is limited. The maximum number of read operations available is about
100,000 times.
OP → INV WRITE (o3-01 = 2)
Copies parameters from the digital operator to the drive.
OP → INV VERIFY (o3-01 = 3)
Compares the parameters in the drive with the parameter settings saved on the digital operator for matches.
The read procedure is described below:
Note: Set o3-02, Copy Allowed Selection, to 1 (Allowed) when performing read functions. Setting o3-02 to 0 disables the Copy
function and protects the parameters saved in the digital operator.
1
Turn on the power supply.
Press
or
to display the parameter setting mode screen, and then press
2
.
Select o3-01 (Copy Function Selection) by
3
.
to select an operation. Select "01" (INV → OP Read) in this
Press
or
4
example.
5
Press
to starts the operation.
After the operation finishes, the screen automatically returns to the copy function
6
selection screen.
7
Press
until the screen returns to the initial screen.
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
Operating Procedure
,
4.9 Checking and Saving Parameter Default Values
or
, and press
LCD Display
Initial setting screen
- MODE -
PRG
Programming
HELP
DATA
FWD
-PRMSET-
PRG
Copy Function Sel
o3-01=
0
*0*
COPY SELECT
FWD
-PRMSET-
PRG
Copy Function Sel
o3-01=
1
*0*
INV→OP READ
0
FWD
READ
INV→OP READING
End
READ COMPLETE
Initial setting screen
4
135