5.4 Fault Detection
Digital Operator Display
dEv
Cause
Load is too heavy.
Acceleration and deceleration times are set too
short.
The load is locked up.
Parameters are not set appropriately.
Motor brake is engaged.
Digital Operator Display
dO
Cause
The panel door is open.
The contact input terminal remains open.
Digital Operator Display
EF0
Cause
An external fault was received from the PLC and
F6-03 was set to a value other than 3 "alarm
only" (the drive continued to run after external
fault).
Problem with the PLC program
Digital Operator Display
EF1
EF2
EF3
EF4
EF5
EF6
EF7
EF8
EF9
EF10
EF11
EF12
152
Speed Deviation (for Control Mode with PG)
The deviation between the speed reference and speed feedback is greater than the setting in
F1-10 for longer than the time set to F1-11.
• Check the size of the load.
• Reduce the load.
Increase the acceleration and deceleration times (C1-01 through C1-08).
Check the machine.
Check the settings of parameters F1-10 and F1-11.
Ensure the motor brake releases properly.
Door Open
The contact input terminal from the door limit switch has detected that the panel door is open.
(Fault detected when the terminal is open. No fault detected when the terminal assigned for
H1-
= 73 is closed.)
Close the panel door.
• Check for disconnected cables and faulty wiring.
• Correct the wiring.
• Check that limit switch is operating normally.
• Replace the limit switch.
Option Card External Fault
An external fault condition is present.
• Remove the cause of the external fault.
• Remove the external fault input from the PLC.
Check the PLC program and correct problems.
External Fault (contact input 1)
External fault input at contact input terminal 1
External Fault (contact input 2)
External fault input at contact input terminal 2
External Fault (contact input 3)
External fault input at contact input terminal 3
External Fault (contact input 4)
External fault input at contact input terminal 4
External Fault (contact input 5)
External fault input at contact input terminal 5
External Fault (contact input 6)
External fault input at contact input terminal 6
External Fault (contact input 7)
External fault input at contact input terminal 7
External Fault (contact input 8)
External fault input at contact input terminal 8
External Fault (contact input 9)
External fault input at contact input terminal 9
External Fault (contact input 10)
External fault input at contact input terminal 10
External Fault (contact input 11)
External fault input at contact input terminal 11
External Fault (contact input 12)
External fault input at contact input terminal 12