Drive Mode Details
n
The following actions are possible in the Drive Mode:
• Run and stop the drive
• Monitor the operation status of the drive (frequency reference, output frequency, output current, output voltage, etc.)
• View information on an alarm
• View a history of alarms that have occurred
Note: To run the drive, select the Drive Mode. Other modes are selectable while the drive is stopped, but the drive will only start
operation when in Drive Mode.
Figure 4.6
illustrates how to change the frequency reference from 0.00 Hz to 6.00 Hz while in the Drive Mode.
Figure 4.6
Frequency reference
display at power up
- MODE -
FREF (OPR)
U1-01= 0.00Hz
U1-02= 0.00Hz
U1-03= 0.00A
JOG
FWD
-MONITR-
FREF (d1-01)
U1-01= 006.00Hz
(0.00 ~ 50.00)
"0.00Hz"
FWD
Note: The drive will not accept a change to the frequency reference until the ENTER key is pressed after the frequency reference is
entered. This feature prevents accidentally setting the frequency reference. To have the drive accept changes to the frequency
reference as soon as changes are made without requiring the ENTER key, set o2-05 to 1.
Programming Mode Details
n
The following actions are possible in the Programming Mode:
• Verify Menu: Check a list of parameters that have been changed from their default values
• Setup Group: Access a list of commonly used parameters to simplify setup (Refer to
Setup Group on page 116
• Parameter Setting Mode: Access and edit all parameter settings
• Auto-Tuning Mode: Automatically calculates and sets motor parameters to optimize drive performance
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
DRV
Rdy
LSEQ
LREF
FWD/REV
Press to select LOCAL
DRV
Rdy
Entry Accepted
Figure 4.6 Setting the Frequency Reference while in the Drive Mode
for details.)
4.3 The Drive and Programming Modes
common_TMonly
F1
-MONITR-
DRV
Rdy
left
FREF (d1-01)
U1-01= 000.00Hz
(0.00 ~ 50.00)
"0.00Hz"
Press until the frequency
FWD
reference changes to 006.00 Hz
-MONITR-
DRV
Rdy
FREF (d1-01)
U1-01= 006.00Hz
(0.00 ~ 60.00)
"0.00Hz"
FWD
F2
right
- MODE -
DRV
Rdy
FREF (OPR)
U1-01= 6.00Hz
ESC
U1-02= 0.00Hz
LSEQ
U1-03= 0.00A
LREF
JOG
FWD/REV
FWD
Simplified Setup Using the
4
115

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for: