YASKAWA FSDrive-MV1000 Series Instructions For Use Manual page 49

Super energy-saving medium-voltage ac drive
Hide thumbs Also See for FSDrive-MV1000 Series:
Table of Contents

Advertisement

1. Insert wire ropes for lifting through the support hook installation openings on the top of the drive.
Figure 2.8
2. Attach the wire ropes for lifting to the support hooks on the transformer to lift the transformer panel.
Figure 2.9
Transformer
support hooks
3. Ensure that the hanging angle is 45°±15°.
DANGER! Do not remove bolts from the top of the transformer panel and fit hoisting tackle to lift it. Failure to comply could result in
deformation or falling of the transformer panel.
DANGER! When lifting the transformer panel, take care to ensure that the housing is not damaged by contact with the ceiling plate
or other parts. Failure to comply could result in deformation of the transformer panel or damage to the ceiling plate.
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
Table 2.8 Transportation Procedure 3 (Class: 3 kV)
Transportation Procedure
Wire ropes for lifting
Drive
Support hook
installation
opening
Top view
Figure 2.8 Inserting Wire Ropes for Lifting
Wire ropes for lifting
Front view
Figure 2.9 Suspension of Transformer Panel
2.2 Mechanical Installation
Front view
Hanging angle of 45°±15°
2
49

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-mv2 series

Table of Contents