4.3 The Drive and Programming Modes
Simplified Setup Using the Setup Group
n
The Setup Group lists the 32 parameters registered as User Parameters. This group expedites the startup process for an
application by showing only the most important parameters. Refer to
Note: For details on the parameters of the setup mode, refer to Chapter 1 Parameter List of the FSDrive-MV1000 Parameter Guide
(TOEP C710687 03).
Figure 4.7
illustrates how to enter and how to change parameters in the Setup Group.
In this example, the Setup Group is accessed to change b1-01 from 1 to 0. This changes the source of the frequency
reference from the control circuit terminals to the digital operator.
Figure 4.7
<1> To edit a parameter set value, go to the right steps.
To confirm the parameter list displayed in the Setup Group, go to the steps below.
<2> To go back to the initial screen, press
To edit another parameter in the Setup Group, press
116
- MODE -
PRG
Quick Setting
HELP
DATA
FWD
- SETUP -
PRG
Application Sel
A1-06= 0
∗0∗
General
Home
FWD
Parameter Display
- SETUP -
PRG
Control Method
A1-02= 2
∗2∗
Open Loop Vector
Home
FWD
<1>
- SETUP -
PRG
Ref Source 1
b1-01= 1
∗1∗
Analog Input
Home
FWD
- SETUP -
PRG
Run Source 1
b1-02= 1
∗1∗
Digital Inputs
Home
FWD
- SETUP -
PRG
StallP Decel Sel
L3-04= 1
∗1∗
General Purpose
Home
FWD
.
or
Figure 4.7 Setup Group Example
Figure 4.7
Rdy
DATA
Rdy
DATA
Rdy
DATA
Entry Accepted
Rdy
DATA
Rdy
DATA
.
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
as an operation example.
- SETUP -
PRG
Rdy
Ref Source 1
∗1∗
b1-01=
1
Analog Input
"1"
FWD
Control Circuit
Terminal
- SETUP -
PRG
Ref Source 1
∗1∗
b1-01=
0
Operator
"1"
FWD
Digital Operator
<2>
Rdy