YASKAWA FSDrive-MV1000 Series Instructions For Use Manual page 245

Super energy-saving medium-voltage ac drive
Hide thumbs Also See for FSDrive-MV1000 Series:
Table of Contents

Advertisement

Register No.
Alarm Contents 3
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
bit 6
00C9H
bit 7, 8
bit 9
bit A
bit B
bit C
bit D
bit E
bit F
Alarm Contents 4
bit 0, 1
bit 2
bit 3
bit 4
bit 5
00CAH
bit 6
bit 7
bit 8
bit 9
bit A
bit B to F
Alarm Contents 5
bit 0 to 3
bit 4
bit 5
00CBH
bit 6, 7
bit 8
bit 9
bit A, B
Alarm Contents 6
bit 0 to 3
bit 4
00CCH
bit 5
bit 6
bit 7 to F
Alarm Contents 7
bit 0 to 2
00CDH
bit 3
bit 4 to F
Alarm Contents 8
bit 0 to 2
bit 3
bit 4 to 7
bit 8
00CEH
bit 9, A
bit B
bit C
bit D
bit E
bit F
00CFH
Reserved
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
Contents
Speed Deviation (dEv)
PG Disconnect (PGo)
Reserved
MEMOBUS/Modbus Communication Error (CE)
Option Communication Error (bUS)
Serial Communication Transmission Error (CALL)
Motor Overload (oL1)
Reserved
Option Card External Fault (EF0)
Motor Switch during Run (rUn)
Reserved
Serial Communication Transmission Error (CALL)
Undertorque Detection 1 (UL3)
Undertorque Detection 2 (UL4)
MEMOBUS/Modbus Test Mode Error (SE)
Reserved
External Fault at contact input terminal 9 (EF9)
External Fault at contact input terminal 10 (EF10)
External Fault at contact input terminal 11 (EF11)
External Fault at contact input terminal 12 (EF12)
PID Feedback Loss (FbL)
Excessive PID Feedback (FbH)
Reserved
Drive Disabled (dnE)
PG Hardware Fault (PGoH)
Reserved
Reserved
Cooling Fan Maintenance Time (LT1)
Capacitor Maintenance Time (LT-2)
Reserved
External Fault at contact input terminal 1 (EF1)
External Fault at contact input terminal 2 (EF2)
Reserved
Reserved
IGBT Maintenance Time (90%) (TrPC)
Soft Charge Bypass Relay Maintenance Time (LT-3)
IGBT Maintenance Time (50%) (LT-4)
Reserved
IGBT Maintenance Time (90%) (TrPC)
Input Overvoltage (IOV)
Reserved
Reserved
Battery Voltage Low (BAT)
Reserved
Transformer Temperature Fault (TMA1)
Reserved
Voltage Unbalance (VUB)
External Fault at contact input terminal 13 (EF13)
External Fault at contact input terminal 14 (EF14)
External Fault at contact input terminal 15 (EF15)
External Fault at contact input terminal 16 (EF16)
C.9 MEMOBUS/Modbus Data Table