Storing Spare Parts - YASKAWA FSDrive-MV1000 Series Instructions For Use Manual

Super energy-saving medium-voltage ac drive
Hide thumbs Also See for FSDrive-MV1000 Series:
Table of Contents

Advertisement

6.7 Spare Parts
Power Cell Related
n
Power Cell Rating
35 A
50 A
70 A
100 A
140 A
200 A
260 A
330 A
400 A
520 A
650 A
Panel Related
n
Part Name
Digital operator
Cooling fan
u Storing Spare Parts
Observe the following precautions to maintain the life and reliability of Power Cells, boards, cooling fans, or other spare
parts when stored:
• Do not unpack the product.
• If the product has been unpacked, enclose the board in a conductive, sealed bag.
• Protect the product not to be directly loaded during storage.
Storage Location
n
Store products held in reserve in a location, such as a warehouse, office, or similar location, with an ambient temperature
of -5 °C to +40 °C, a relative humidity no greater than 85%, and without condensation or freezing. For storage over short
periods (approximately one month), for example during transportation, a temperature range of -20 to +60 °C is
permissible.
Avoid storing the products in the areas with the following characteristics:
• Exposure to direct sunlight.
• Subject to shock and vibration during transportation.
• Dust and oil mist, such as a cement factory or spinning mill.
• Corrosive gas, such as a chemical factory, refinery, or sewage plant.
• A risk of salt damage, such as a location near the sea, or in salt damaged areas.
Preventing Power Cell Deterioration
n
Apply voltage to a reserve Power Cell smoothing capacitor every six months to avoid deterioration.
Use a customer-supplied variable power supply and step-up transformer to apply voltage. Increase the voltage gradually
over two to three minutes and continue to apply the voltage for at least one hour with no load.
AC Variable Power Supply (Single-phase/Three-phase) on page 209
page 209
for details.
After installing a spare Power Cell into the drive panel and using it for the first time, leave the main circuit power supply
on continuously for 20 minutes after voltage was first applied to the Power Cell to stabilize the Power Cell capacitors.
Note: 1. Use a variable power supply with a step-up transformer.
2. A variable power supply and step-up transformer is to be provided by the customer.
208
Table 6.8 Power Cell Spare Parts
Procurement Code
7910251-1010
7910251-1020
7910251-1030
7910251-1040
7910251-1050
7910251-1060
7910251-1070
7910251-1080
7910251-1090
7910251-1100
7910251-1110
Table 6.9 Panel Spare Parts
Model
JVOP-180
S3G250-BC54-01
S3G400-KC22-71
S3G500-AM56-21
Model
JESD-MV2S12035
JESD-MV2S12050
JESD-MV2S12070
JESD-MV2S12100
JESD-MV2S12140
JESD-MV2S12200
JESD-MV2S12260
JESD-MV2S12330
JESD-MV2S12400
JESD-MV2S12520
JESD-MV2S12650
Varies depending on the drive capacity. Refer to
Models and Number of Cooling Fans Used on
page
and
When Using a DC Variable Power Supply on
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
Specifications
1200 Vac, 35 A rating
1200 Vac, 50 A rating
1200 Vac, 70 A rating
1200 Vac, 100 A rating
1200 Vac, 140 A rating
1200 Vac, 200 A rating
1200 Vac, 260 A rating
1200 Vac, 330 A rating
1200 Vac, 400 A rating
1200 Vac, 520 A rating
1200 Vac, 650 A rating
Remarks
200.
Refer to When Using an

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cimr-mv2 series

Table of Contents