98
Example Configuration
9.1.1.3
Testing Process Data Exchange
The device must be configured correctly to test the exchange of process data
successfully. When LED E of the master flashes a constant green, there is a
connection between master and slave.
1.
Close the Bluetooth
2.
Right-click on the master and slave one after the other.
3.
Select Process Data in the context menu. The process data dialog opens
where you can view the raw data.
Right-click on the word Bluetooth
4.
the dialog.
You can choose between Input Data, Output Data and Reset. From now on, you
can switch between the display for input and output data using this menu (see
figure "View of the process data").
Figure 47: View of the process data
5.
Select Output Data for one of the 750-644 I/O modules. Enter any test data
in the "Output" dialog by double-clicking in the required table field to
enable overwrite.
(In the process image from offset + 2, byte 0 and 1 are reserved for status
information.)
6.
Select Input Data for the other 750-644 I/O module. The "Input" dialog
opens.
7.
Check if the output data of the one 750-644 I/O module leads to the correct
input data in the other 750-644 I/O module.
9.1.2
Startup via Mailbox Commands in the Process Data Dialog
In addition to using the Bluetooth
use Mailbox commands to configure 750-644 I/O modules. Mailbox commands
are entered using function blocks in the WAGO-I/O-PRO CAA or in the process
data dialog of WAGO-I/O-CHECK. WAGO-I/O-CHECK is used here.
®
parameterization dialog.
®
RF Transceiver in the table headers of
®
parameterization dialog, it is also possible to
Version 2.0.0, valid from FW/HW Version 03/03
WAGO-I/O-SYSTEM 750
®
750-644 Bluetooth
RF-Transceiver
Manual