Parameter Sets; Process Of Parameter Transmission - WAGO I/O-SYSTEM 750 Manual

Bluetooth rf-transceiver
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
®
750-644 Bluetooth
RF-Transceiver
Parameters
A0 ... A7
TGL_MS
PRM_RW
MORE_SM
TGL_SM
TIMEOUT
BUF_OVF
PRM_ERR
RES
6.3.4.3

Parameter Sets

For use of the parameter channel, parameter sets are defined and indexed using
parameter addresses (A7 ... A0). Module-specific parameters (parameters 0
through 249) and general system parameters (parameters 250 through 255) are
differentiated.
6.3.4.4

Process of Parameter Transmission

Parameter data is exchanged between the application and 750-644 I/O module via
request/response process. The application initiates an instruction using the toggle
bit (TGL_MS != TGL_SM). The application then queries the communication
control register (R57) of the 750-644 I/O module until the I/O module confirms
execution of the instruction (TGL_SM == TGL_MS).
The possible instructions to the parameterization interface of the 750-644 I/O
module are listed in below:
Manual
Version 2.0.0, valid from FW/HW Version 03/03
Value
Description
range
0 ... 255
Word address of the parameter to be read / to be written.
FALSE,
Toggle bit to release new instructions from the application to
TRUE
the 750-644 I/O module. If TGL_SM and TGL_MS have the
same status, no new instruction has been released yet. If the
flags have different statuses, a new instruction has been
released and is currently being processed.
FALSE
Parameter data of A7 ... A0 is read.
TRUE
Parameter data is written to A7 ... A0.
FALSE
End of parameter transmission.
TRUE
More parameter data to follow.
FALSE,
Toggle bit indicating that a parameter sent by the 750-644 I/O
TRUE
module has been transferred. If TGL_SM and TGL_MS have
different statuses, the corresponding instruction is processed
by the 750-644 I/O module. If both flags have the same
status, the instruction for the parameter that was sent or
requested is completed.
FALSE
The transmission of the parameters has been completed
within the stipulated time (parameter address 0).
TRUE
The maximum time for the transmission of the parameters
between 750-644 I/O module and application was exceeded.
FALSE
Access to the write and read buffer of the 750-644 I/O
module were permitted.
TRUE
Parameters outside of the write or read buffer were accessed.
FALSE
The parameter/all parameters previously transmitted are valid.
TRUE
At least one transmitted parameter was defective. The flag
can either be set after each parameter that is received or after
the transmission of the parameters is completed.
FALSE
Reserved for expansions.
Process Image
63

Advertisement

Chapters

Table of Contents
loading