Commissioning
Use the [>>] button to move the selected devices to the real-time or ad-hoc
•
list. MAC IDs or devices names can be moved from the list of available
devices to the ad-hoc or real-time list by drag & drop.
Use the [<<] button to remove the configured devices from the real-time or
•
ad-hoc list. You can also double-click the respective MAC ID to delete the
devices.
The tables on the Net Forming page are populated as follows:
Table 45: Table identifiers in Net Forming
Designation
ID
MAC Address
Device Name
Slot
UserFriendlyName
Bind
UserFriendlyName
Please note when assigning a "UserFriendlyName" that to display the entire
length of the name, a Mailbox size of 18 bytes is necessary. With a smaller
Mailbox setting, the full name is actually displayed within WAGO-I/O-CHECK,
but not completely saved, so when the name is read back from the 750-644 I/O
module, not all the characters are displayed.
8.1.5.3
PI Mapping
To make settings on the PI Mapping page, the process image size of the master
must first be set.
Use the [Configuration] button in the toolbar to open the "Data Frame" dialog
for entering the process image and Mailbox sizes:
Figure 32: Data Frame dialog
You can make the following settings:
Input/selection
_ _
_ _ : _ _ : _ _ : _ _ : _ _ : _ _
ASCII characters
_
ASCII characters
Yes
No
Version 2.0.0, valid from FW/HW Version 03/03
WAGO-I/O-SYSTEM 750
®
750-644 Bluetooth
RF-Transceiver
Description
ID of the device in available
devices
MAC address of the device
Device name (cannot be
changed)
Slot number of the assigned
devices
Name assigned to a slot (can
be changed)
Bind device ("Yes")
Do not bind device ("No")