Use in Hazardous Environments
Table 73: Description of marking example for approved I/O modules according to NEC 500
Printing on Text
CL I
DIV 2
Grp. ABCD
Op temp code T4
Pos : 94 /All e Seri en (Allgemei ne Module)/Eins atz in Ex- Ber eichen/Errichtungs besti mmungen @ 3\mod_1232453624234_21.doc x @ 26370 @ 2 @ 1
11.2

Installation Regulations

Pos : 95 /All e Seri en (Allgemei ne Module)/Eins atz in Ex- Ber eichen/Errichtungs besti mmungen Einl eitung @ 3\mod_1232453837234_21.doc x @ 26374 @ @ 1
In the Federal Republic of Germany, various national regulations for the
installation in explosive areas must be taken into consideration. The basis for this
forms the working reliability regulation, which is the national conversion of the
European guideline 99/92/E6. They are complemented by the installation
regulation EN 60079-14. The following are excerpts from additional VDE
regulations:

Table 74: VDE installation regulations in Germany

DIN VDE 0100 Installation in power plants with rated voltages up to 1000 V
DIN VDE 0101 Installation in power plants with rated voltages above 1 kV
DIN VDE 0800 Installation and operation in telecommunication plants including
DIN VDE 0185 lightning protection systems
The USA and Canada have their own regulations. The following are excerpts
from these regulations:

Table 75: Installation regulations in USA and Canada

NFPA 70
ANSI/ISA-RP 12.6-1987 Recommended Practice
C22.1
Pos : 96 /Serie 750 ( WAGO-I/O-SYST EM)/Eins atz in Ex- Ber eichen/Achtung: Errichtungs besti mmungen Seri e 750 beac hten @ 3\mod_1224158893890_21.doc x @ 24191 @ @ 1
Notice the following points
When using the WAGO-I/O SYSTEM 750 (electrical operation) with Ex
approval, the following points are mandatory:
Pos : 97 /Serie 750 ( WAGO-I/O-SYST EM)/Eins atz in Ex- Ber eichen/Bes ondere Bedi ngungen für den sic heren ATEX- und IEC-Ex- Betrieb gem. DEM KO 08 ATEX 142851X & IECEx @ 7\mod_1274277358920_21.doc x @ 56642 @ 3 @ 1
11.2.1
Special Conditions for Safe Operation of the ATEX and IEC
Ex (acc. DEMKO 08 ATEX 142851X and IECEx PTB 07.0064)
The fieldbus-independent I/O modules of the WAGO-I/O-SYSTEM 750-.../...-...
must be installed in an environment with degree of pollution 2 or better. In the
final application, the I/O modules must be mounted in an enclosure with IP 54
degree of protection at a minimum with the following exceptions:
Description
Explosion protection group (condition of use
category)
Area of application
Explosion group (gas group)
Temperature class
information processing equipment
National Electrical Code Art. 500 Hazardous Locations
Canadian Electrical Code
Version 2.0.0, valid from FW/HW Version 03/03
WAGO-I/O-SYSTEM 750
®
750-644 Bluetooth
RF-Transceiver
Manual