ABB SACE Tmax XT5 Operation And Maintenance Manual page 154

Tmax low voltage moulded-case circuit-breakers xt5
Hide thumbs Also See for SACE Tmax XT5:
Table of Contents

Advertisement

Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
152 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
communication:
Parameter
Description
Preferred configuration
If several configuration files are present, allows file hierarchy between
.cid and .iid to be defined
file
Allows the IEEE 1588 protocol for distribution of the clock and
Enable IEEE 1558
synchronization signal to be enabled
Enables the module to be set up as a master in the the network
IEEE 1558 Master
segment to which it belongs (synchronization clock).
IEEE 1558 Delay
Allows the data exchange mode between module and master, either
mechanism
Peer-to-Peer or End-to-End, to be selected.
Time zone
Defines the time zone to be used for synchronism
Used to select whether daylight saving time is present (ON) or not
Daylight Saving Time
(OFF) in the country to which the synchronization time refers
Defines the file loading procedure:
• TFTP always On = port open, loading always possible
• TFTP enable required = port normally closed. To start loading,
TFTP Security level
Enable TFTP must be run at the start of the procedure and Disable
TFTP must be run at the end of the procedure (disable not necessary,
security command).
Defines the limitations to remote opening and closing command
execution:
CB Open/CB Close
• Standard commands = standard commands (unrestricted) activated
• CB operate request = standard commands not activated. Use
command
programmable functions YC COMMAND and YO COMMAND, and
Request breaker open (28) and Request breaker close (29) commands
Falg word hex
Sets a filter on the selectivity statuses
communication:
Information
HW and Boot version
Flash CRC status and result
Ekip Link status
SNTP Server Error
SNTP Server Synchronization
IEEE 1558 status
GOOSE Missing
Configure Mismatch
Decode Error
Sequence number error
Remote programmable statuses
(from E to R)
Zone selectivity remote inputs
.
(1)
Description
General module information
Information about the correctness of the SW in the module
Signals Ethernet cable connection errors
Error in communication with SNTP server
State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
Master Active) or absence (PTP Master but Passive) of a higher level
master
Signals that an expected GOOSE has not been received
A GOOSE received does not conform to the expected structure
Condition (true/false) of the programmable states and information on
selectivity arising from logic defined in the configuration files loaded in
module IEC 61850
ABB | SACE Tmax XT
Default
.cid
OFF
OFF
End-to-
End
+00:00
OFF
TFTP
always On
Standard
commands
0
External accessories | 10 - Ekip Com IEC 61850

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents

Save PDF