Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
189 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
correctly:
Information
Description
SN and version
Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time of
connection to the network in the case of configuration with a dynamic IP, or can be set
IP address
via the menu in the event of a static IP.
NOTE: without a DHCP server, the module automatically adopts a random IP
address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the modules
Network Mask
belong and enables modules to be searched for within a defined set of recipients.
Gateway
IP address of the node to which the module is connected, in the presence of several
address
subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
communication:
Information
Description
Parameter for changing the configuration of the module from Server
Only to Client and Server and for integrating it into an interactive data
Client/Server
exchange network (see Ekip Com Hub on page 191).
IMPORTANT: if Client/Server, the module allows data
exchange like a normal Server function
Allows the IEEE 1588 protocol for distribution of the clock and
Enable IEEE 1558
synchronization signal to be enabled
Enables the module to be set up as a master in the the network
IEEE 1558 Master
segment to which it belongs (synchronization clock).
IEEE 1558 Delay
Allows the data exchange mode between module and master, either
mechanism
Peer-to-Peer or End-to-End, to be selected.
Allows the SNTP protocol for distribution of the clock and
Enable client SNTP
synchronization signal to be enabled
ANTP Server
Allows the network server that supplies the SNTP to be set.
address
Time zone
Defines the time zone to be used for synchronism
Daylight Saving
Used to select whether daylight saving time is present (ON) or not
Time
(OFF) in the country to which the synchronization time refers
Permits (Enabled ARP) the periodic generation of a Gratuituos ARP
Disable Gratuitous
message, used by Ekip Connect to rapidly find the modules via
ARP
Ethernet scan without knowing the IP address beforehand
Password protected
Enables the writing operations performed via the network to be
access
protected by a password (Request password)
Password Modbus
With access protected by enabled password, this is the password to
TCP
use before each writing session
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2)
the parameter can only be changed via system bus in the remote configuration
.
(1)
(1)
.
(2)
Internal accessories | 6 - Ekip Link
ABB | SACE Tmax XT
Default
Server only
Off
Off
End-to- End
Off
0.0.0.0
+00:00
Off
ARP Enabled
Standard
mode
Local access