Interface the module has three signaling leds:
Input parameters All the available inputs enable the following parameters to be configured:
162 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Output Ekip Touch can be configured so that the contacts of each output are closed or opened upon the occurrence
of one or more events, with different programming options (page 162).
The output of each module consists of 2 contacts (K11-K12 and K13-K14 for model 2K-1; K21-K22 and
K23-K24 for model 2K-2; K31-K32 and K33-K34 for model 2K-3), which are isolated from the unit and from
the other outputs, and have the following electrical characteristics:
Characteristics
Maximum switchable voltage
Breaking capacity
Dielectric strength between open contacts
Dielectric strength between each contact and coil
(1)
data relating to a resistive load
Figure 52
LEDs
Power
I 11, I 12
O 11, O 12
Menu The specific configuration area will activate in the Settings - Modules menu if the Ekip Signalling 2K module
is detected correctly by Ekip Touch.
A specific menu containing the submenus of all the available and configurable inputs and outputs is available
for each Ekip Signalling 2K module detected by Ekip Touch.
Parameter
Polarity
Delay
Description
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
and communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Indicate the status of the contacts of each output:
• off: contact open
• on: contact closed
Indicate the status of the contacts of each input:
• off: circuit open
• on: short circuit
Description
Defines whether the input is interpreted as ON by Ekip Touch when it is
open (Active open) or when it is closed (Active Closed)
Minimum activation time of the input before status change is recognized;
the delay is given in seconds and can be set within range: 0 s to 100 s, in
0.01 s steps
NOTES:
• if the input is deactivated before this time has elapsed the status
change is not recognized
• if delay = 0 s status change must still be more than 300 µS
Maximum limit
(1)
150 VDC / 250 VAC
2 A @ 30 VDC, 0,8 A @ 50 VDC, 0,2 A @ 150 VDC,
4A @ 250 VAC
1000 V AC (1 minute @ 50 Hz).
1000 V AC (1 minute @ 50 Hz).
External accessories | 13 - Ekip Signalling 2K
ABB | SACE Tmax XT
Default
Active
closed
0.1 s