ABB SACE Tmax XT5 Operation And Maintenance Manual page 118

Tmax low voltage moulded-case circuit-breakers xt5
Hide thumbs Also See for SACE Tmax XT5:
Table of Contents

Advertisement

BLE - Parameters The menu, which is available in Settings-Modules, enables the Bluetooth antenna on the Trip unit to be
Test Bus The parameter allows parameter editing via the service connector to be enabled/disabled, thereby limiting
System The System menu provides various options:
116 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
activated. This is useful for launching a communication with an external device (tablet, smartphone) according
to the BLE protocol, via the Ekip Connect Mobile APP (page 14).
The following parameters are available
Parameter
Description
Enables/disables LV antenna switch-on and availability of the Battery mode
parameter in the menu:
Enable
• if On, the LV antenna comes on, on the basis of the Battery Mode
parameter configuration
• if Off, the antenna is off
Defines the switch-on mode of the LV antenna, based on the presence of
devices on the service connector (Ekip T&P, Ekip Programming, Ekip TT);
can have two values:
• --- ; with this option, the status of the LV antenna depends esclusively on
the presence of devices: on if not present; off if present
• ON ; with this option, the antenna is switched off for 15 seconds when
Battery mode
a device is connected, after which: it remains off if communication with
the device has been activated; it comes on if no communication has been
activated
IMPORTANT: the typical scenario in which Battery mode should
be configured = On is: Ekip Touch + Ekip TT + communication
with smartphone activated; in all other cases, including System
Update, configure Battery mode = ---
IMPORTANT: when LV antenna is on, communication on the service connector is not
available
the possibility of configuring all the options on the display (in the Local mode) or via modules Ekip Com (in
the Remote mode).
Disabling the parameter, Local mode and using the password allow security against undesired modification
by unauthorized persons to be increased.
NOTE: with Test Bus= Off, communication via service connector is still guaranteed (reading
enabled)
Ekip Touch is supplied with the parameter set to: On.
Parameter
Description
Date
Setting the current date
Time
Setting the current time
Language
Setting the language in display menus
Password
Password setting (page 37)
IMPORTANT: setting and checking Date and Time is important for all the recording
functions (trips or measurements); in the event of date and time glitches, reset and
if necessary replace the battery inside Ekip Touch (page 19).
ABB | SACE Tmax XT
Default
Off
---
Default
English
00001
Settings | 1 - Main settings

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents