View The View menu provides various options:
Maintenance The parameter allows an alarm, concerning maintenance of the unit, to be enabled/disabled. (page 100).
MLRIU The MLRIU parameters are available with Ekip M Touch for the Motor Protections functions (page 68).
117 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Parameter
Description
Enables the orientation of the Alarms List, Measuring Instruments and
Main Measurements pages to be set. The options are: Horizontal, Vertical
TFT orientation
clockwise, Vertical counter-clockwise
Allows you to activate a supplementary information page, which can
be accessed by pressing the iTEST button twice from any page with a
Customer page
diagnosis bar. The information on the new page can be configured via Ekip
Connect (page 119)
Allows the current to be displayed in the Measuring instruments page to be
set from among the following options: Imax, I1, I2, I3, Ne (only in the 4P or
Ammeter Phase
3P + N configuration)
Allows the voltage to be displayed in the Measuring instruments page to be
Voltmeter Phase
set from among the following options: Vmax, V12, V23, V31
Ekip Touch is supplied with the parameter set to: On.
NOTE: to ensure correct operation, check where applicable: presence and status of the
outgoing connections, those towards the Trip unit of Ekip CI and the relative output contact
(O61)
Parameters
Parameter
Description
Allows the TRIP mode to be set (page 38):
• Heavy: in the event of a TRIP, it is controlled by the Trip coil of the CB
• Normal: contact O61 of the Ekip CI module is opened in the event of a
TRIP
NOTES:
Open Mode
• the TRIP for protections G or I always involves the Trip coil
command, regardless of the Open Mode configuration
• in the Normal mode, if the Trip unit detects the presence of a fault
even after the open command sent to O61, a command is also sent to
the Trip coil of the CB
Autoreclosure
When Open Mode= Normal, allows re-closing of contact O61 to be activated
Enabled
after a TRIP due to protection L (On)
Allows the trip class of the motor to be selected from among: 5E, 10E, 20 E,
Motor Class
30E (page 68)
Defines the time waited, after the open command of contact O61, before
the fault is considered to be still present and action is taken by sending a
Contactor Delay
command to the Trip coil of the CB. The value is given in seconds and can
be set within the range: 0.1 s to 1 s, in 0.1 s steps
Defines the time waited after the open command of contact O61, before
Autoreclosure
this latter is closed. The value is given in seconds and can be set within the
Time
range: 1 s to 1000 s, in 1 s steps
ABB | SACE Tmax XT
Default
Horizontal
Off
Imax
Vmax
Default
Standard
Off
0,1
60
Settings | 1 - Main settings