20 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Continued from the previous page
Signal
Suggestions
Unit on with auxiliary supply, Local Bus parameter enabled but connection to modules
not present, incorrect or communication lost (for more than five seconds); check:
Local bus
• connection and powering of modules in terminal box or external
• that the moldules connected are compatible with Ekip Touch
• that the Local Bus parameter is: ON details on page 115).
Trip fail command
CB has failed to open and/or current still present after a TRIP command: comply with
(BF)
the procedure proposed in the next chapter 'Faults, causes and remedies'
Check:
• Rating plug of model compatible with Ekip Touch and CB size
• If present, protection parameters do not conflict with size of current of unit details
Configuration
on page 38)
• In the absence of Vaux threshold I4 and/or I41 > 100 A
• In the absence of Vaux time t4 and/or t41 > 100 ms
Invalid Date
Wrong date and time: set in Settings-System-Date and Settings-System-Time
Problem of Ekip Com Hub module with: certificates, connected devices, missing
Ekip Com Hub
Com modules (RTU or with Ethernet connection), API TLS device, Hub events, parsar
configuration
Ekip Link Bus
Fault in Ekip Link module: check loss of connection with one or more actors
Ekip Signalling 3T
Alarm for connection of one or more analog inputs to Ekip Signalling 3T module
Internal error
Internal error; contact ABB if this typoe of error occurs
Fault with Ekip Com modules: synchronization problem of SNTP synchronization
SNTP error
reference module
Measuring Error
Ekip Measuring parameter reading error, contact ABB
Ethernet
No external cable on one or more Ekip Com modules with Ethernet connection
disconnected
IEEE1588 synch
Synchronization problem of IEEE 1588 synchronization reference module
MAC Address
Ekip Com module detected with incorrect / not allowed MAC address
Measuring
Install Ekip Measuring module (Settings-Circuit breaker-Installation-Measuring-Install)
installation
menu
Install Rating Plug (Settings-Circuit breaker-Rating Plug-Install menu) and check
RatingPlugInstallation
connection if there are further faults
Maintenance
Maintenance alarm: check whether set maintenance interval has elapsed
PC Power exceed The average power limit setting of the Power Controller has been exceeded
Rating plug
Rating plug not present or size incompatible with Ekip Touch parameters
Zone Selectivity
Error in zone selectivity connections (Hardware Selectivity)
Diag
Sensor L1/L2/
Fault in connection of sensors to Trip unit; check status of sensors, including external
L3/Ne
Neutral, or call ABB
Configuration
TFTP server enabled and/or configuration session open on module Ekip Com
Session
IEC61850 or Ekip Hub
CB status
CB state incorrect (esample: current present but CB in open state)
Switchboard Actor
communication
Check configuration and connection of Ekip Link module
Error
TC disconnected
Check Trip coil, status of the terminal and cables connecting to Ekip Touch
Contact Wear
Make sure that the contacts/poles are in good condition.
Continued on the next page