11 - Performance table

General notes:
Standard Protections
79 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
• The performance values given in the next table are valid with Δ 100 ms trip time, temperature and signals
within the operating limits; failure to comply with these limitations could lead to an increase in the tolerances.
• Ekip Touch sends the TRIP command if the signal read exceeds the threshold for longer than the set time
(or the time resulting from the calculation formula)
• With an inverse time-delay trip curve, the calculation refers to a signal with a constant value throughout
the timing: variation of the alarm signal causes a different trip time
• The additional notes are given after all the tables
Protection
Trip time t
[ANSI code]
(with curve t = k / I
L [49]
(with curves 60255-151)
t
= t2 ( with curve t = k )
t
S [50TD / 51]
(with curve t = k / I
S2 [50TD]
t
= t5
t
≤ 30 ms
I [50]
t
t
t
= t4 ( with curve t = k )
t
G [50N TD / 51N]
(with curve t = k / I
MCR
t
≤ 30 ms
t
≤ 30 ms
2I [50]
t
t
IU [46]
t
= t6
t
Startup
Protection
Trip time t
[ANSI code]
S StartUp
t
= t2 startup
t
≤ 30 ms
I StartUp
t
t
G StartUp
t
= t4 startup
t
S2 StartUp
t
= t5 startup
t
Trip threshold
(1)
tolerance
(3)
t
)
2
Activation for If within
range: (1.05 to 1.2) x I1
with If ≤ 6 In: ± 7 % /
with If > 6 In: ± 10 %
)
2
with If ≤ 6 In: ± 7 % /
with If > 6 In: ± 10 %
± 10 %
± 7 %
)
2
± 10 %
± 10 %
± 10 %
Trip threshold
tolerance
(3)
t
with If ≤ 6 In: ± 7 % /
with If > 6 In: ± 10 %
± 10 %
± 7 %
with If ≤ 6 In: ± 7 % /
with If > 6 In: ± 10 %
ABB | SACE Tmax XT
Trip time tolerance
with If ≤ 6 In: ± 10 % /
with If > 6 In: ± 20 %
The best between
± 10% and 40 ms
with If ≤ 6 In: ± 15 % /
with If > 6 In: ± 20 %
The best between
± 10% and 40 ms
--
The best between
± 10% and 40 ms
(2)
± 15 %
--
--
with t6 ≤ 5 s: ± 100 ms /
with t6 < 5 s the best between
± 10 % and ± 40 ms
Trip time tolerance
The best between
± 10% and 40 ms
--
The best between
± 10% and 40 ms
The best between
± 10% and 40 ms
Protections | 11 - Performance table