ABB SACE Tmax XT5 Operation And Maintenance Manual page 197

Tmax low voltage moulded-case circuit-breakers xt5
Hide thumbs Also See for SACE Tmax XT5:
Table of Contents

Advertisement

Input parameters The input can be configured in the Settings-Modules-Ekip Signalling 1K-Input menu:
Output parameters The output can be configured in the Settings-Modules-Ekip Signalling 1K-Output menu:
About The About-Modules menu contains the specific menu of the module, in which the statuses of the input (On/
195 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Parameter
Description
Defines whether the input is interpreted as ON by the Trip unit when it
Polarity
is open (Active open) or when it is closed (Active Closed)
Minimum activation time of the input before status change is
recognized; the delay is given in seconds and can be set within range:
0 s to 100 s, in 0.01 s steps
Delay
Parameter
Description
Event which activates the output and switches the contacts.
Different protection proposals, statuses and thresholds are available
Signal source
on the display; the Custom mode can be configured via Ekip Connect
so as to extend the solutions and combine several events
Minimum duration of the presence of the source before the output is
activated; the delay is given in seconds and can be set within range: 0
s to 100 s, in 0.01 s steps
Delay
Defines the rest status of the contact with source not present
Contact Type
between: open (NO) and closed (NC)
Allows the output (and relative status led) to be kept activated (On) or
Latched
(1)
deactivated (Off) when the event disappears
Defines the minimum closing time of the contact following the rapid
presence of sources
• Source duration < min. activation = contact is activated for the
min Activation
minimum activation time
Time
(2)
• Source duration ≥ min. activation = contact is activated for as long
as the source persists
Choose between: 0 ms, 100 ms, 200 ms
(1)
deactivate the latchings of the outputs used if Ekip Measuring is used for the Power Controller function
(2)
if Ekip Measuring is used for the Power Controller function, the Pulse Mode option will also be available; if
selected, the output is kept activated for a set time that depends on the function, regardless of whether the
event that activated it persists
Off) and output (Open/Closed) are present.
Test The output test command can be executed in the Test menu (see page 121).
NOTES :
• status change is not recognized if the input deactivates before
this time has elapsed
• if delay = 0 s status change must still be more than 300 µS
NOTE:
• the output will not be switched if the source is deactivated
before this time has elapsed
• if delay = 0 s the source must still be present for longer than
300 µS
ABB | SACE Tmax XT
Default
Active closed
0.1 s
Default
None
0 s
NO
Off
0 ms
Internal accessories | 8 - Ekip Signalling 1K