2 - Ekip Com Modbus TCP

Safety and cyber security Since the module allows the actuator connected to Ekip Touch and access to the data in the unit to be
Connections To connect the module to its communication network and for references about the terminals, please consult
177 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Ekip Com Modbus TCP is a communication accessory which allows Ekip Touch to be integrated into an
Ethernet network with Modbus TCP communication protocol, with remote supervision and monitoring
functions in two different modes, standard and HTTP server.
The module is configured as master and remotely, you can:
• read Ekip Touch measurements and information
• provide information about the status of the circuit-breaker (open, closed, tripped)
• manage certain controls, including opening and closing the actuator (MOE-E)
• access information and parameters not available on the display
NOTE: the remote open and close commands of the circuit-breaker can only be executed if
Ekip Touch is in the Remote configuration
The System Interface document is available for mapping the module in its communication network. All the
required communication and command details are listed in the document (page 129).
Depending on the parameter settings, described in the next pages, the ports used by the module are:
Port
Service
502/TCP
Modbus TCP
80/TCP
Server HTTP
319/UDP
IEEE 1588
320/UDP
68/UDP
DHCP client
IMPORTANT: each circuit-breaker can house one module only; configuration with
external communication modules is not allowed if an internal module is present.
checked, it can only be connected to networks equipped with all the necessary security and prevention
measures against unauthorized access (for example, the network of the control system of an installation).
IMPORTANT:
• it is the customer's sole responsibility to provide and continuously ensure a secure
connection between the module and customer network or any other network (as the
case may be). The plant manager must establish and maintain appropriate measures
(such as but not limited to the installation of firewalls, application of authentication
measures, encryption of data, installation of antivirus programs, etc.) to protect the
product, the network, the customer system and interface against any kind of security
breaches, unauthorized access, interference, intrusion, loss and/or theft of data or
information.ABB and its affiliates are not liable for damages and/or losses related to
such security breaches, unauthorized accesses, interference, intrusion, loss and/or
theft of data or information.
• The module cannot be connected directly to the Internet. Only connect to dedicated
Ethernet networks with Modbus TCP communication protocol
document 1SDM000005A1001.
The module is supplied with a 1-meter length cable and cabled RJ45 connector for interfacing with its
network.
To connect the module to Ekip Touch, please consult document 1SDH002011A1503.
Notes
Valid for the Modbus TCP mode
Valid for the HTTP Server mode
Valid with IEEE 1588 protocol enabled
DHCP client enabled alternatively as: Static address = On
ABB | SACE Tmax XT
Internal accessories | 2 - Ekip Com Modbus TCP