Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
Remote information Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
186 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
communication:
Parameter
Description
Preferred
If several configuration files are present, allows file hierarchy
between .cid and .iid to be defined
configuration file
Allows the IEEE 1588 protocol for distribution of the clock and
Enable IEEE 1558
synchronization signal to be enabled
Enables the module to be set up as a master in the the
IEEE 1558 Master
network segment to which it belongs (synchronization clock).
IEEE 1558 Delay
Allows the data exchange mode between module and master,
mechanism
either Peer-to-Peer or End-to-End, to be selected.
Time zone
Defines the time zone to be used for synchronism
Used to select whether daylight saving time is present (ON)
Daylight Saving
or not (OFF) in the country to which the synchronization time
Time
refers
Defines the file loading procedure:
• TFTP always On= port open, loading always possible
• TFTP enable required= port normally closed. To start
TFTP Security level
loading, Enable TFTP must be run at the start of the procedure
and disable TFTP must be run at the end of the procedure
(disable not necessary, security command)
Defines the limitations to remote opening and closing
command execution:
• Standard commands= standard commands (unrestricted)
CB Open/CB Close
activated
command
• CB operate request= standard commands not activated.
Use programmable functions YC COMMAND and YO
COMMAND, and Request breaker open (28) and Request
breaker close (29) commands
Falg word hex
Set a filter on the selectivity statuses
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
communication:
Information
HW and Boot version
Flash CRC status and result
Ekip Link status
SNTP Server Error
SNTP Server Synchronization
IEEE 1558 status
GOOSE Missing
Configure Mismatch
Decode Error
Sequence number error
Remote programmable statuses
(from E to R)
Zone selectivity remote inputs
.
(1)
Description
General module information
Information about the correctness of the SW in the module
Signals Ethernet cable connection errors
Error in communication with SNTP server
State of synchronism with SNTP server
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP
Master Active) or absence (PTP Master but Passive) of the higher level
master
Signals that an expected GOOSE has not been received
A GOOSE received does not conform to the expected structure
Condition (true/false) of the programmable states and information on
selectivity arising from logic defined in the configuration files loaded in
module IEC 61850
ABB | SACE Tmax XT
Default
.cid
Off
Off
End-to-End
+00:00
Off
TFTP always On
Standard
commands
0
Internal accessories | 5 - Ekip Com IEC 61850