Power supply Ekip Com EtherNet/IP
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
182 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
is supplied directly by the Ekip Touch module to which it is connected.
TM
NOTE: communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
available in the Settings menu (page 33).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter
Static IP address ON
Static address IP address
Static Network Mask
Static Gateway address
correctly:
Parameter
Description
SN and version
Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
IP address
can be set via the menu in the event of a static IP.
Subnet mask; identifies the method for recognizing the subnet to which the
Network Mask
modules belong and enables modules to be searched for within a defined set
of recipients.
IP address of the node to which the module is connected, in the presence of
Gateway address
several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
communication:
Parameter
Enable IEEE 1558
IEEE 1558 Master
IEEE 1558 Delay mechanism
Enable client SNTP
ANTP Server address
Time zone
Daylight Saving Time
NOTE: Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Description
Defines whether the module has a dynamic (Off) IP address
or static (On) IP address
Se = On all the associated parameters are enabled
Enables the static IP to be selected
Enables the subnet mask to be selected
When there are several subnets, enables the IP address of
the node to which the module is connected to be selected
NOTE: without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx range
Description
Allows the IEEE 1588 protocol for distribution of the clock
and synchronization signal to be enabled
Enables the module to be set up as a master in the the
network segment to which it belongs (synchronization
clock).
Allows the data exchange mode between module and
master, either Peer-to-Peer or End-to-End, to be selected.
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled
Allows the network server that supplies the SNTP to be set. 0.0.0.0
Defines the time zone to be used for synchronism
Used to select whether daylight saving time is present (ON)
or not (OFF) in the country to which the synchronization
time refers
ABB | SACE Tmax XT
Default
Off
0.0.0.0
0.0.0.0
0.0.0.0
Default
Off
(NOTE)
Off
End-to-End
Off
.
(NOTE)
+00:00
Off
Internal accessories | 4 - Ekip Com EtherNet/IP TM