Ekip CI The menu activates in the presence of module Ekip CI, auxiliary power supply and local bus enabled.
Ekip Signalling 2K The menu activates in the presence of module Ekip Signalling 2K, auxiliary power supply and local bus
Ekip Signalling 1K The menu includes the Autotest command which, in the presence of Ekip Signalling 1 K / MM and auxiliary
ZoneSelectivity The menu has one or two sections, visibility of which depends on the protections available and enabled:
121 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
The Autotest command is available in the menu; its selection activates the test of the leds and output contact
O61 in sequence:
1.
Led reset and closing of contact O61 (if open)
2.
Lighting up of all leds in sequence and successive switch-off
3.
Opening of the O61 contact, switching on and off of the O61 led
4.
Re-closing of O61 contact
IMPORTANT:
• the autotest sequence also includes transmission of the open command of the output contact:
the user is responsible for checking that it has opened correctly
• the test sequence always ends with the closing of the O61 contact, regardless of the starting
condition: verify that the change of status following the test does not create problems in your
installation.
enabled.
NOTE: a menu is available for each Ekip Signalling 2K module present, up to a maximum of
three
The Autotest command is available in each submenu; it activates the automatic output test (Contacts and
leds), input test (leds) and provides for the following operations:
1.
Resetting of output contacts (= open) and leds (= off).
2.
Lighting up of all leds in sequence (output and input)
3.
Closing and switch-off in sequence of the two output contacts while the relative leds come on.
4.
Reset initial conditions
IMPORTANT: the Autotest command closes the contacts regardless of the configuration
set by the user: the user is responsible for making the devices connected to the Ekip
Signalling 2K modules secure, checking that the contacts have closed properly and
that the leds have come on
power supply, commands an automatic open-close-open sequence of the module contact.
IMPORTANT: the command closes the contact regardless of the configuration set by
the user: the user is responsible for making the devices connected to the Ekip
Signalling 1K module secure and checking that the contact has closed properly
Submenus
S Selectivity
G Selectivity
Each submenu has three fields for checking selectivity inputs and outputs:
Field
Input
Force output
Force Output
Consult the description of the putting into service procedure when checking the selectivity contacts (page
17).
Reference selectivity
S, S2, D (Forward)
G, Gext, D (Backward)
Description
Provides the status of the selectivity input (On/Off)
Selectivity output activated
Selectivity output deactivated
ABB | SACE Tmax XT
Outputs/Inputs managed
SZi (DFi), SZo (DFo)
GZi (DBi), GZo (DBo)
Test | 1 - Test