ABB SACE Tmax XT5 Operation And Maintenance Manual page 144

Tmax low voltage moulded-case circuit-breakers xt5
Hide thumbs Also See for SACE Tmax XT5:
Table of Contents

Advertisement

Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
142 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
available in the Settings menu (page 114).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter
Description
Function
Defines the mode between Modbus TCP and HTTP Server
Defines whether the module has a dynamic (Off) IP address or static
Static IP
(On) IP address
address ON
Se = On all the associated parameters are enabled
Static address
Enables the static IP to be selected
IP address
Static Network
Enables the subnet mask to be selected
Mask
Static Gateway
When there are several subnets, enables the IP address of the node to
address
which the module is connected to be selected
correctly:
About
Description
SN and version
Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time of
connection to the network in the case of configuration with a dynamic IP, or can be
IP address
xset via the menu in the event of a static IP.
NOTE: without a DHCP server, the module automatically adopts a random IP
address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the modules
Network Mask
belong and enables modules to be searched for within a defined set of recipients.
IP address of the node to which the module is connected, in the presence of several
Gateway address
subnets
TCP Client 1, 2, 3
IP addresses of the client devices connected to the module (in the Server mode)
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
ABB | SACE Tmax XT
Default
Modbus TCP
Off
0.0.0.0
0.0.0.0
0.0.0.0
External accessories | 7 - Ekip Com Modbus TCP