ABB SACE Tmax XT5 Operation And Maintenance Manual page 48

Tmax low voltage moulded-case circuit-breakers xt5
Hide thumbs Also See for SACE Tmax XT5:
Table of Contents

Advertisement

2I Protection
t
I31
46 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Function
If the current of one or more phases exceeds threshold I31 and a trip event is present, the protection
transmits the TRIP command after a non-programmable fixed time.
2I
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 79)
• the graph with trip curve (page 86)
Parameter
Description
Activates/deactivates the protection and its availability in the
I
Enable
parameters menu.
Establishes the value that activates the protection.
The value is given as both absolute value (A) and relative value (In) and
Threshold I31
can be set within the range: 1.5 In to 15 In, in 0.1 In steps
Protection enabling makes the 2I Mode section available in the Advanced - Functions menu, where the
protection activation event can be configured:
Parameter
Description
Two alternative modes are available:
• Dependent function: the protection is activated if the programmed
Activation
activation event has occurred; this configuration makes the function
and delay parameters available
• Activated: the protection is always activated
The activation event between the input contacts of Ekip Signalling 2K,
the statuses of the unit (open/closed) and the Custom function can be
selected
Function
Protection activation delay calculated from the presence of the
activation event onwards.
The value is given in seconds and can be set within the range: 0 s to
Delay
100 s, in 0.1 s steps
Commands by remote control
Two further temporary protection activation/deactivation commands are available when the unit is connected
to one or more Ekip Com modules:
• 2I ON Mode: activates the protection
• 2I OFF Mode: deactivates the protection
Consult the unit System Interface 1SDH002031A1101 for details.
NOTE: if the protection has been activated by command 2I ON Mode, it is deactivated by
command 2I OFF Mode or when the unit shuts down
Signallings
When protection 2I is activated, the message "2I active" appears in the diagnostic bar and in the Alarm List
page, and the alarm led will be on steady.
NOTE: Ekip Connect allows the Custom function to be
customized so as to associate the activation event with up to
eight statuses in AND or OR configuration
NOTE: the protection trips if the event is present for longer than
the set time lag
ABB | SACE Tmax XT
Default
OFF
1,5 In
Default
Dependent
function
Disabled
0 s
Protections | 1 - Standard Protections

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents