1 - Standard Protections

39 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Elenco The Standard protections available for all Ekip Touch models, are:
Name
Type of protection
L
Overload with inverse long-time delay
S
Selective short-circuit
S2
Short-circuit with adjustable delay
(3)
I
Instantaneous short-circuit
G
Earth fault with adjustable delay
(1)
MCR
Instantaneous short-circuit on circuit-breaker closing 45
2I
Instantaneous short-circuit programmable
IU
Current unbalance
Neutral
Different protection on neutral phase
(2)
Harmonic
Distorted waveforms
distortion
T
Abnormal temperatures
Hardware Trip
Internal connection errors
Current
Control thresholds exceeded
thresholds
(1)
not available with LSI version of Ekip Touch
(2)
not available with Ekip M Touch
(3)
not available with Ekip G Touch