Additional functions

1 - Power Controller

Description The Power Controller function allows the loads of an installation to be managed according to power
Ekip Touch Parameter Certain configuration parameters of the function are available in the Settings - Power Controller menu 33).
Ekip Touch Measure A specific page containing the main measurements is available in the Measurements pages, with Power
122 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
consumption, for the purpose of reducing consumption and optimizing energy efficiency.
All the parameters and measurements of the function are available via Ekip Connect; however, the Trip unit
allows certain of them to be set and displayed, as described below.
IMPORTANT: consult the Technical catalog or White paper of the function for full
details (page 4, 13).
Parameter
Description
Enable
Activates/deactivates the function and its availability in the parameters menu OFF
Enables the configuration of each of the 15 programmable loads to be set
Load Operating
(from Load 1 to Load 15); either Automatic or Manual configuration can be
Mode
selected
Enables 10 power limits to be set (from Power Limit 1 to Power Limit 10);
Power Limits
the value is given in kW and can be set within range: 10 kW to 10000 kW, in
10 kW steps
NOTE: to characterize the parameters of the function, it is advisable to first configure them
via Ekip Connect and only then use the Trip unit to enable or modify the power limits and
loads
Controller activated:
Measurement
Ea
ΔT
LOADS
LOADS Shed
Sp
T
The Power Controller menu, with information concerning the 15 loads in two submenus, is available in the
About page when Power Controller is activated (page 34):
Submenus
Load Input Status
Load Active
Description
Expected energy
Time elapsed in the evaluation window
Number of loads monitored
Number of shed loads
Load shedding priority setting
Evaluation window
Information provided
Status of the loads (from Load 1 to Load 15): open or closed
Load configuration (from Load 1 to Load 15): active or inactive
ABB | SACE Tmax XT
Default
Manual
10 kW
Additional functions | 1 - Power Controller