ABB SACE Tmax XT5 Operation And Maintenance Manual page 157

Tmax low voltage moulded-case circuit-breakers xt5
Hide thumbs Also See for SACE Tmax XT5:
Table of Contents

Advertisement

Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
Remote configurations Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
155 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
available in the Settings menu (page 33).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter
Static IP address ON
Static address IP address
Static Network Mask
Static Gateway address
correctly:
Information
Description
Identifier and SW version of the module
SN and version
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
can be set via the menu in the event of a static IP.
IP address
Subnet mask; identifies the method for recognizing the subnet to which the
modules belong and enables modules to be searched for within a defined set
Network Mask
of recipients.
IP address of the node to which the module is connected, in the presence of
Gateway address
several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
communication:
Parameter
Description
Parameter for changing the configuration of the module from Server
Only to Client and Server and for integrating it into an interactive
data exchange network (see Ekip Com Hub on page157).
Client/Server
Allows the IEEE 1588 protocol for distribution of the clock and
Enable IEEE 1558
synchronization signal to be enabled
Enables the module to be set up as a master in the the network
IEEE 1558 Master
segment to which it belongs (synchronization clock).
IEEE 1558 Delay
Allows the data exchange mode between module and master,
either Peer-to-Peer or End-to-End, to be selected.
mechanism
Allows the SNTP protocol for distribution of the clock and
Enable client SNTP
synchronization signal to be enabled
ANTP Server address
Allows the network server that supplies the SNTP to be set.
Time zone
Defines the time zone to be used for synchronism
Used to select whether daylight saving time is present (ON) or not
Daylight Saving Time
(OFF) in the country to which the synchronization time refers
Description
Defines whether the module has a dynamic (Off) IP address or
static (On) IP address
Se = On all the associated parameters are enabled
Enables the static IP to be selected
Enables the subnet mask to be selected
When there are several subnets, enables the IP address of the
node to which the module is connected to be selected
NOTE: without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx range
IMPORTANT: if Client/Server, the module allows data
exchange like a normal Server function
ABB | SACE Tmax XT
.
(1)
(1)
Continued on the next page
External accessories | 11 - Ekip Link
Default
OFF
0.0.0.0
0.0.0.0
0.0.0.0
Default
Server only
OFF
OFF
End-to-End
Off
0.0.0.0
+00:00
OFF