Connections To connect the module to its communication network and for references about the terminals, please consult
Power supply Ekip Com IEC 61850 is supplied directly by the Ekip Touch to which it is connected.
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
185 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
circuit diagrams 1SDM000005A1001.
The module is supplied with a 1-meter length cable and cabled RJ45 connector for interfacing with its
network.
To connect the module to Ekip Touch and to actuator MOE-E if present, please consult document
1SDH002011A1503.
NOTE: communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
available in the Settings menu (page 33).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter
Description
Defines whether the module has a dynamic (Off) IP address or
Static IP address ON
static (On) IP address
Se = On all the associated parameters are enabled
Static address IP address Enables the static IP to be selected
Static Network Mask
Enables the subnet mask to be selected
When there are several subnets, enables the IP address of the
Static Gateway address
node to which the module is connected to be selected
Allows the SNTP protocol for distribution of the clock and
Enable SNTP client
synchronization signal to be enabled.
SNTP Server Addr.
Allows the network server that supplies the SNTP to be set.
correctly:
Information
Description
SN and version
Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
IP address
can be set via the menu in the event of a static IP.
Subnet mask; identifies the method for recognizing the subnet to which the
Network Mask
modules belong and enables modules to be searched for within a defined set
of recipients.
IP address of the node to which the module is connected, in the presence of
Gateway address
several subnets
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
MAC address
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Cfg file
Name of the configuration file uploaded to the modules
Code of the error concerning the configuration file (0 = no error)
Cfg file error
NOTE: without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx range
ABB | SACE Tmax XT
Default
Off
0.0.0.0
0.0.0.0
0.0.0.0
Off
0.0.0.0
Internal accessories | 5 - Ekip Com IEC 61850