7 - Ekip Com Hub

Safety and cyber security The module uses the HTTPS protocol and can be connected to the Internet
Connections To connect the module to its communication network and for references about the terminals, please consult
191 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Ekip Com Hub is a communication accessory that enables the data and measurements of Ekip Touch and
other devices connected to the same installation to be gathered and then made available on the server
through an Ethernet network.
The configuration of the module is available via Ekip Connect or with the System Interface document, which
contains all the details. (page 129).
The ports used by the module are:
Port
Service
67/UDP 68/UDP
DHCP client
443/TCP
HTTPS
123/TCP
SNTP
53/TCP
DNS
Ekip Link also provides information about the status of the circuit-breaker (open, closed, tripped).
IMPORTANT: each circuit-breaker can house one module only; configuration with
external communication modules is not allowed if an internal module is present.
IMPORTANT:
• it is the customer's sole responsibility to provide and continuously ensure a secure
connection between the module and customer network or any other network (as the
case may be). The plant manager must establish and maintain appropriate measures
(such as but not limited to the installation of firewalls, application of authentication
measures, encryption of data, installation of antivirus programs, etc.) to protect the
product, the network, the customer system and interface against any kind of security
breaches, unauthorized access, interference, intrusion, loss and/or theft of data or
information.ABB and its affiliates are not liable for damages and/or losses related to
such security breaches, unauthorized accesses, interference, intrusion, loss and/or
theft of data or information.
circuit diagrams 1SDM000005A1001.
The module is supplied with a 1-meter length cable and cabled RJ45 connector for interfacing with its
network.
To connect the module to Ekip Touch and to actuator MOE-E if present, please consult document
1SDH002011A1503.
Notes
DHCP client enabled as an alternative to Static address = On
always active when module is enabled
active with SNTP client enabled