Remote information Certain additional information concerning the version and status of the module is available via the service
176 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the Settings menu (page 33).
Two areas are activated if Ekip Touch detects the module correctly:
• information area in the About-Modules menu, containing the software version and serial number of the module
• specific configuration area in the Settings-Modules menu, where the following communication parameters
can be configured:
Parameter
Description
Module address; 1 to 247 range available
Serial address
Data transmission speed; 3 options are available: 9600 bit/s, 19200
Baudrate
bit/s, 38400 bit/s
Defines the stop and parity bit; 4 options are available:
• 8,E,1 = 8 data bits, 1 EVEN parity bit, 1 STOP bit
Physical
• 8,O,1 = 8 data bits, 1 ODD parity bit, 1 STOP bit
protocol
• 8,N,2 = 8 data bits, no parity bit, 2 STOP bits
• 8,N,1 = 8 data bits, no parity bit, 1 STOP bit
NOTE: 247 default of Ekip Com Modbus RTU module
connector (via Ekip Connect) or by communication via system bus; the information includes: HW and Boot
version, CRC status (correctness of the SW in the module).
IMPORTANT: devices connected to the same network
must have different addresses
ABB | SACE Tmax XT
Default
247
19200 bit/s
8,E,1
Internal accessories | 1 - Ekip Com Modbus RTU