Input Trip reset Digital input I63 (H63 and H64) allows contact O61 to be re-opened after a TRIP.
Interface The module has four signaling leds:
Menu Local bus activation, which is essential for starting communication between the module and Trip unit, is
173 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
The module permits two logic statuses, interpreted differently by the Trip unit on the basis of the polarity
configured by the user:
Electrical
State
condition
Open
Circuit open
Closed
Short-circuit
The re-closing command is activated at the front.
Figure 55
Parameter
Description
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on
Power
and communication with trip unit present
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with trip unit absent
status of input for temperature probe PT100 I61:
• off: input disabled
I 61
• on: input enabled and sensor present
• flashing: input enabled and sensor disconnected or signal not valid
Indicates the status of the digital input for Trip Reset I63:
I 63
• off: input open
• on: input closed
Indicates the status of the command contact of remote control switch O61:
O 61
• off: contact closed
• on: contact open
available in the Settings menu (page 33).
The specific configuration, measurement, test and information areas will activate in the respective menus if
the Ekip CI module is detected correctly by Ekip Touch.
Status detected
Polarity
(and command required)
Active open
On (O61 open command)
Active closed
Off
Active open
Off
Active closed
On (O61 open command)
K
ABB | SACE Tmax XT
External accessories | 16 - Ekip CI