Power supply Ekip Com Modbus TCP is supplied directly by the Ekip Touch module to which it is connected.
Configurations via menu Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
Information in menu The following information will be available in the About-Modules menu if Ekip Touch has detected the module
178 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
NOTE: communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Mode The two operating modes available can be configured via the menu:
Mode
Description
Information and commands are managed by single requests/queries according to
Modbus TCP
Modbus TCP rules and mapping (see System Interface)
Information and commands are available in a web page, which can be accessed via a
browser by entering the IP Address of the module as the address.
HTTP Server
The page has a login window where the user is requested to enter the same user
password as the one requested on the display for editing parameters.
available in the Settings menu (page 129).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the Settings-Modules menu:
Parameter
Function
Static IP address ON
Static address IP address
Static Network Mask
Static Gateway address
correctly:
Information
SN and version
IP address
Network Mask
Gateway address
TCP Client 1, 2, 3
MAC address
Description
Defines the mode between Modbus TCP and HTTP
Serverdbus TCP (see System Interface)
Defines whether the module has a dynamic (Off) IP address
or static (On) IP address
Se = On all the associated parameters are enabled
Enables the static IP to be selected
Enables the subnet mask to be selected
When there are several subnets, enables the IP address of
the node to which the module is connected to be selected
Description
Identifier and SW version of the module
Address of the module, assigned to the module by a DHCP server at the time of
connection to the network in the case of configuration with a dynamic IP, or can be
set via the menu in the event of a static IP.
NOTE: without a DHCP server, the module automatically adopts a random IP
address within the 169.254.xxx.xxx range
Subnet mask; identifies the method for recognizing the subnet to which the modules
belong and enables modules to be searched for within a defined set of recipients.
IP address of the node to which the module is connected, in the presence of several
subnets
IP addresses of the client devices connected to the module (in the Server mode)
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
ABB | SACE Tmax XT
Default
Modbus TCP
Off
0.0.0.0
0.0.0.0
0.0.0.0
Internal accessories | 2 - Ekip Com Modbus TCP