Parameters 2 The Datalogger 1 and Datalogger 2 submenus (available if the number of dataloggers selected is: 2) contain
Signallings If there is a recording present, Ekip Touch provides the information on the diagnosis bar (DataLog available).
Ekip Connect Ekip Connect 3 has two specific areas for the Datalogger function:
106 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
the following options:
Parameter
Description
Trigger event at which the recording is to be interrupted; the main
protection options (trips, timings, alarms) and the actuator status
Stop Event
(open/closed) are displayed.
The Custom option can be configured via Ekip Connect
Recording interruption delay, calculated from the trigger; the value is
Stop delay
given in seconds and can be set within a range: 0 s to 10 s, in 0.01 s
steps
Restart
Recording start command
Stop
Manual recording stop command
Memory Type
Ekip Connect enables the Memory Type (Non volatile/Volatile) to be selected:
• Non volatile: Ekip Touch maintains the recording even when off; the life of the internal battery of the unit
may noticeably shorten with respect to the declared value if there is a recording in the memory but no
auxiliary supply.
• Volatile: Ekip Touch loses the recording if it is switched off; when the unit is switched on again, the datalogger
automatically restarts, losing the previously stored data.
The parameter is configured by default as Non volatile.
NOTE: Ekip Touch provides a general indication of recording availability in the configuration
with 2 dataloggers: use Ekip Connect to identify which of the 2 recordings (or both) is available
• Datalogger for configuring the recording parameters with a user-friendly interface, and for downloading
the recordings
• Data Viewer for opening and consulting the recordings
Both areas are available in the Tools menu of Ekip Connect.
ABB | SACE Tmax XT
Default
None
0.01 s
Measurements | 4 - Datalogger