ABB SACE Tmax XT5 Operation And Maintenance Manual page 20

Tmax low voltage moulded-case circuit-breakers xt5
Hide thumbs Also See for SACE Tmax XT5:
Table of Contents

Advertisement

Check accessories The inspections to perform on the external and internal accessories, if present, before putting into service
18 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
are indicated below:
Accessories
Checks
1. If Ekip Cartridge is present: check the connections of all modules to Ekip Supply and
the connection between Ekip Cartridge and the lateral terminal box of the CB
For Ekip Signalling 10K and Ekip Multimeter, in the absence of Ekip Cartridge: check the
connection of the bus of the module (W3-W4) to the lateral terminal box of the CB
2. Power up Ekip Touch (and the external modules if there is a separate supply) and
External
make sure they are on
modules
3. Check that the Local bus is enabled (Settings-Modules-Local Bus)
4. Check that the Power Led of each module is on like the Power Led of Ekip Touch
(steady or synchronous flash)
5. Check in the About-Modules menu to make sure that all installed modules are present
and that there are no alarms
1. make sure that module is connected to the internal terminal box
2. Make sure that the auxiliary supply is connected to the internal terminal box
Internal modules
3. Power up the Trip unit and make sure it is on
4. Check in the About-Modules menu to make sure that all installed modules are present
and that there are no alarms
1. Check that the sensor is connected to the lateral terminal box of the CB in the proper
way and that the terminals are in the right direction
2. Power up the Trip unit and make sure it is on
External neutral
3. Check in the Settings-Circuit-breaker menu that Configuration= 3P + N; otherwise
change the parameter
4. Make sure there are no alarms
1. Check selectivity connections (between Ekip Touch and the other units) as shown in
circuit diagrams 1SDM000002A1001
2. Provide Ekip Touch with auxiliary power and make sure that CB status is: Open
3. Check that the protection of the selectivity concerned has been enabled (example: S
protection)
4. Select the Zone Selectivity menu and the submenu of the protection concerned;
follow the instructions in points 5, 6, 7 and 8 for each protection activated
NOTE: for selectivity D, consider submenu S for the Forward connections and G
for the Backward connections
Zone selectivity
Check Output:
5. Select the Force Output command and check, on the Trip unit connected to the Ekip
Touch output, that the status of its Input = ON
6. Select the Release Output command and check, on the Trip unit connected to the
Ekip Touch output, that the status of its Input = OFF
Check Input:
7. Select the Force Output command on the Trip unit connected to the Ekip Touch input
and check on Ekip Touch that the status of its Input = ON
8. Select the Release Output command on the Trip unit connected to the Ekip Touch
input and check on Ekip Touch that the status of its Input = OFF
1. Make sure that the MOE-E stored energy operating mechanism is correctly cabled as
shown in circuit diagrams 1SDM000002A1001
2. Set the circuit-breaker to the closed position
MOE-E
3. Provide Ekip Touch with auxiliary power and supply the MOE-E device with rated
stored energy
voltage
operating
4. Perform an opening test from the Test-Test CB menu with the Open CB) command
mechanism
and check that the CB has opened
5. Repeat the test from the Test-Test CB menu with the Close CB) command and check
that the CB has closed
AUP circuit
1. Check that Trip unit reads status of withdrawable circuit breaker properly by means of
breaker status
About-Circuit breaker-CB Status
inputs, if CB is
2. Switch status of AUP device and make sure that Trip unit reads the status change
withdrawable
properly by means of About-Circuit breaker-CB status menu
version
(1)
for details consult document
1SDH001000r0506
ABB | SACE Tmax XT
(1)
Management operations | 1 - Putting into service