8 - Ekip Signalling 1K

Connections The circuit diagrams and references concerning the terminals are available in document 1SDM000005A1001.
Power supply Ekip Signalling 1K is supplied directly by the Ekip Touch to which it is connected.
194 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Ekip Signalling 1K is a signaling accessory allowing programmable inputs/outputs to be managed.
The module can be configured in the CB with the IEC standard.
IMPORTANT: each circuit-breaker can house one module only; configuration with
external modules is not allowed if an internal module is present
To connect the module to Ekip Touch and to actuator MOE-E if present, please consult document
1SDH002011A1507.
WARNING! communication between Ekip Touch and the module is interrupted in the
absence of auxiliary power supply
Input The input can be configured so that its status corresponds to actions or signals, with different programming
options (see Menu).
The module permits two logic statuses, interpreted differently by the Trip unit on the basis of the selected
configuration:
State
Electrical condition
Open
Circuit open
Short-circuit
Close
Output The output has three contacts: normally open (NO), normally closed (NC) and common.
The output can be configured so that the contacts change status when one or more events occur, with
different programming options (see Menu).
Compared to the common contact, the NO and NC contacts have the following electrical characteristics:
Characteristics
Maximum switchable voltage
Breaking capacity
Dielectric strength between contact and internal coil 1000 V AC (1 minute @ 50 Hz).
(1)
data relating to a resistive load
Contact configuration
Active open
Active closed
Active open
Active closed
Maximum limit
(1)
150 VDC / 250 VAC.
2 A @ 30 VDC, 0,8 A @ 50 VDC, 0,2 A @ 150 VDC,
4A @ 250 VAC
Internal accessories | 8 - Ekip Signalling 1K
ABB | SACE Tmax XT
Status detected by
Trip unit
ON
OFF
OFF
ON