2 - Load Shedding

Description The Load Shedding function allows faults to be managed in installations which are able to function thanks
Ekip Touch Parameter Certain configuration parameters of the function are available in the Settings - Load Shedding menu (page33).
123 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
to the energy produced by renewable and local energy sources, especially the absence of power supply
caused, for example, by a fault on the MV voltage side.
This function is available in two versions:
• Basic, supplied with all the Ekip Touch Trip units
• Adaptive; can be purchased by means of the relative additional package and is available for all Trip units
with the Measuring Measurements package, except Ekip M Touch
All the parameters and measurements of the function are available via Ekip Connect; however, the Trip unit
allows certain of them to be set and displayed, as described below.
IMPORTANT: consult the Technical catalog or White paper of the function for full
details (page 4, 14).
NOTE: it is advisable to first configure the parameters via Ekip Connect, and only then operate
on the Trip unit
Parameter
Description
Enable
Activates/deactivates the function and its availability in the parameters menu Off
Display of the version of the function, Basic or Adaptive
Version
NOTE: with the Basic version, the only parameter available is
Reconnection Timeout
Solar Plant
Establishes whether the microgrid includes a solar energy system (Off/On)
present
Available with Solar Energy System Present = On, defines the rated power of
Solar Plant
its solar energy system.
Nominal Power
The value is given in kW and can be set within the range: 100 kW to 65535
kW, in 1 kW steps
ATS
Establishes whether the installation has an ATS system (Off/On)
Available with ATS=On, defines the power received from the ATS branch;
Generator Power
can be set within the range: 0 kW (. . . .) to 10000 kW, in 1 kW steps
Defines the instantaneous frequency variation that activates Load shedding
Frequency slope
The value is given as absolute value (Hz/s) and can be set within the range:
0.6 Hz/s to 10 Hz/s in 0.2 Hz/s steps
Control threshold of the minimum frequency that activates Load shedding
F W Warning
The value is given as absolute value (Hertz) and can be set within the range:
(1)
0.9 Fn to 1.1 Fn in 0.001 Fn steps
Defines the time employed by the Trip unit between reconnection of one load
Reconnection
and the next, after the main CB has reclosed. The value is given as absolute
Timeout
value (s) and can be set within the range: 10 s to 1800 s, in 1 s steps
NOTE: Load shedding activates if the monitoring conditions defined by the Frequency slope
and F W Warning parameters are present at the same time
ABB | SACE Tmax XT
Default
--
Off
100 kW
Off
. . . .
0,6 Hz/s
3 Fn
10 s