Ekip Com Hub - ABB SACE Tmax XT5 Operation And Maintenance Manual

Tmax low voltage moulded-case circuit-breakers xt5
Hide thumbs Also See for SACE Tmax XT5:
Table of Contents

Advertisement

12 - Ekip Com Hub

Safety and cyber security The module uses the HTTPS protocol and can be connected to the Internet
Connections For references about the connection and terminals, please consult document 1SDM000005A1001; a cable
Power supply Ekip Com Hub is supplied directly by the Ekip Supply module to which it is connected.
157 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Ekip Com Hub is a communication accessory that enables the data and measurements of Ekip Touch and
other devices connected to the same installation to be gathered and then made available on the server
through an Ethernet network.
The configuration of the module is available via Ekip Connect or with the System Interface document, which
contains all the details. (page 129).
The ports used by the module are:
Port
Service
67/udp 68/udp
DHCP client
443/tcp
HTTPS
123/udp
SNTP
53/udp
DNS
The Ekip Com Modbus RTU and Ekip Com Modbus TCP modules can be configured to support Ekip Com
Hub in the collection of data to send to Cloud. See Getting Started 1SDC200063B0201.
Accessories Ekip Cartridge and Ekip Supply are required in order to connect Ekip Com Hub to Ekip Touch
(page 130, 131).
IMPORTANT:
• it is the customer's sole responsibility to provide and continuously ensure a secure
connection between the module and customer network or any other network (as the
case may be). The plant manager must establish and maintain appropriate measures
(such as but not limited to the installation of firewalls, application of authentication
measures, encryption of data, installation of antivirus programs, etc.) to protect the
product, the network, the customer system and interface against any kind of security
breaches, unauthorized access, interference, intrusion, loss and/or theft of data or
information. ABB and its affiliates are not liable for damages and/or losses related to
such security breaches, unauthorized accesses, interference, intrusion, loss and/or
theft of data or information.
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication bus.
To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SDH002009A1503.
NOTE: communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Notes
DHCP client enabled alternatively as Static address = On
Always active when module is enabled
Active with SNTP client enabled
Always active